1 loop addressable fire detection control panel for the management of addressable type systems. The loop allows the connection of 99 detectors and 99 modules. Output sounder controlled, relay output for general alarm and fault. One serial output for download/upload programming or printer option. Graphic display with 8 rows by 20 columns. Programmable text 16 characters each point and 16 characters each zone. 50 geographical zones and 100 groups with logical operators (AND, OR, DEL, etc...). 500 events archive. Auto programming of the loop with double address recognition. Signal for maintenance requirements for the detectors. CPD approved according to EN 54-2 and EN 54-4. Power supply 230VAC. Standard Power Supply 1.8A. 1A at 24VDC auxiliary power. 12VDC charging of two batteries 7Ah. Dimensions 366mm x 265mm x 111mm.